At least once a year, starting when the damper is installed. Dampers in dusty or greasy ductwork may need testing more often, and health buildings can use a planned sampling cycle agreed with their fire safety team.

The law does not give a number. The Fire Safety Order only says fire safety equipment must be maintained and kept working, and leaves the detail to standards.

The usual answer: every year

The standard most fire risk assessors work to is BS 9999. As BESA summarises it, dampers should be tested by a competent person when they are installed and then at intervals of no more than one year. Spring-operated dampers should be drop tested each time.

For an ordinary office, school or block of flats with clean supply and extract air, a yearly visit is the norm and is what most firms will quote for.

When once a year is not enough

The same guidance says dampers in dusty or polluted conditions may need testing more often. In practice that means:

  • Kitchen extract ductwork, where grease builds up on blades and tracks.
  • Workshops, laundries and anywhere with lint or fine dust.
  • Buildings where previous tests found several dirty or sticking dampers.

Six-monthly testing is common in these settings. If your last report shows a pattern of failures for the same reason, ask the tester whether a shorter interval would be cheaper than repeated repairs.

Hospitals and health buildings

Health buildings follow HTM 03-01 as well. The IHEEM technical guidance sets out a risk-based approach: critical dampers checked yearly, and lower-risk dampers tested in a rolling sample so that every one is covered within a set cycle. Any failure is recorded, fixed quickly and fed back into the fire risk assessment.

A sampling plan needs agreeing with whoever is responsible for fire safety on the site, and the register should show which year each damper falls in.

After building work

Any time ductwork, ceilings or partitions are altered, the dampers nearby should be checked before the area is handed back. Contractors fixing cables or pipes are a common cause of blocked dampers.

Keeping track

The easiest way to stay on time is a register with a next-due date for every damper. Our test log template has a column for it. For what the rules say in full, see the regulations page, and for booking the visit itself, a fire damper testing company can quote from your damper count.

Sources for this article

Tell us where the dampers are

Give us the building postcode and who to speak to. A damper count, a recent report or a ceiling plan all help the firm price it, but none of that is needed to start.

We look for a damper testing firm that works in your area and let you know which one before anything else happens. Your details reach that firm only once you agree, and there is no charge to you.

Your building and contact details
Get a quote