The tester reaches the damper, checks its fixing and condition, releases the fusible link so the blades fall shut, confirms it closes and latches fully, then reopens it, refits the link and records the result with photos.
A drop test is the core of an annual damper visit for spring-operated dampers. It is simple to describe and easy to do badly, so it helps to know what a proper one involves.
1. Reach the damper
The tester opens the ceiling hatch and the access door in the duct. If there is no panel, the damper is recorded as no access, not skipped. Getting in is often the slowest part of the visit.
2. Look before touching
Before anything moves, the tester checks the damper is the right one on the register, that the frame is fixed and fire-stopped into the wall or floor, and that nothing such as a cable, screw or pipe is fixed through it. A photo is taken with the damper open.
3. Release the link
The tester releases or removes the fusible link. The spring should pull the blades shut on their own, quickly and fully, and the latch should hold them closed. Helping the blades by hand defeats the point of the test.
4. Confirm it closed
The tester looks along the duct to check the blades have fully closed with no gap, and takes a second photo. A damper that stops part way, closes slowly or bounces open is a fail.
5. Reset
The blades are reopened, the spring rewound and a link fitted. A new link is used if the old one is damaged, painted or the wrong rating. The damper is checked to make sure it sits fully open and does not restrict the airflow.
6. Record the result
Each damper gets one line: tag, location, type, result, photo references and any defect. BESA guidance is behind the expectation that every damper is tested and recorded, not a sample, unless a planned sampling regime applies.
Common reasons for a fail
- Dust or grease on the blades or tracks.
- A weak or broken spring.
- Links painted over or wired open.
- Distorted frames or blades.
- Something fixed through the damper.
What happens next is covered on our maintenance and repairs page. For a firm that does this work, BESA keeps a Vent Hygiene Register, and a fire damper testing company can arrange the whole visit.