A damper without access cannot be tested, so the first step is a report that lists every no-access damper. The usual fix is two panels, one in the duct and one in the ceiling or shaft, fitted by someone who keeps any fire rating intact, ideally in the same visit as other repairs.
This is the most common problem in damper testing. The damper exists, it is on the drawings, but there is no hatch in the ceiling or no door in the duct, and the tester cannot reach it.
First, get it on paper
A no-access damper is not a pass and it should never be left off a report. Each one should be listed with its location and the reason it could not be reached. That list is what you need to plan and price the fix, and it shows your fire risk assessor you know where the gaps are. The duty to keep equipment in good repair under the Fire Safety Order still applies to a damper nobody can see.
The options
Open the ceiling each time. In a grid ceiling the tester can lift tiles. That works, but it is slower and may damage tiles. In plasterboard ceilings it means cutting and making good every year, which costs more over time than fitting a panel once.
Fit an access panel in the duct. Many older dampers were installed with no access door in the ductwork. A door can usually be fitted next to the damper, sized so the tester can see and reach the blades and link.
Fit an access panel in the ceiling or shaft. Where the ceiling or riser wall is fire-rated, the panel must carry the same rating, otherwise you have made a new hole in the fire separation. That is a job for someone who knows passive fire protection, and Approved Document B is the reference for performance.
Replace with a different damper. Occasionally a damper is in such an awkward place that replacing it with a motorised unit tested from a panel is the better long-term choice. Physical checks are still needed, so access is not avoided altogether.
Planning the work
- Group the no-access dampers by floor or area and fit panels in one programme.
- Combine panel fitting with any other remedials, while ceilings are open.
- Retest each damper as soon as its panel is in, so it moves from no access to pass.
- Update the register with the panel location.
Cost
There are no published standard prices for access panels, because they depend on the ceiling, the duct size and the fire rating. Ask for them as a separate line. Our cost guide shows the published prices for the test itself, and a fire damper testing company can survey the no-access list and price it panel by panel.